Transmitter Type | Isolated Universal Programmable |
Accuracy | Pt100, mV and mA: 0.2 % of span, T/C: 0.2% of span ±1 °C (±1.8 °F) |
Input Type | J, K, T, N, R, S, B, E, Pt100, 0-50 mV, 0-10 V, 0-20 mA and 4-20 mA |
Output Type | 0-10 Vdc |
Response Time | 500 ms |
Thermal Drift | 0.003% of span / °C |
Isolation Input-Output | 1 kVca |
Electric Protection | Reverse Polarity |
Programmable Functions | Input Type, Programmable Range, Electric grid filter, Offset, Sensor Failure |
USB Configuration | Through TxConfig adapter |
Configuration Software | TxConfig |
Approvals / Regulations | CE, NAMUR NE43, RoHS, Reach |
Operating Conditions | -40 to 85 °C (-40 to 185 °F), 0 to 90% RH |
Power Supply | 4-20 mA Loop Powered (12 - 35 Vdc) |
Enclosure Material | ABS |
Dimensions | 77 mm x 72 mm (3.03 in x 2.83 in) |
Format / Mounting | 35 mm (T535) DIN Rail |
Sensor Type |
Voltage | - Maximum Measurement Range: 0 to 50 mV
- Minimum Measurement Range: 5 mV
|
Thermocouple K | - Maximum Measurement Range: -150 to 1370 °C
- Minimum Measurement Range: 100 °C
|
Thermocouple J | - Maximum Measurement Range: -100 to 760 °C
- Minimum Measurement Range: 100 °C
|
Thermocouple R | - Maximum Measurement Range: -50 to 1760 °C
- Minimum Measurement Range: 400 °C
|
Thermocouple S | - Maximum Measurement Range: -50 to 1760 °C
- Minimum Measurement Range: 400 °C
|
Thermocouple T | - Maximum Measurement Range: -160 to 400 °C
- Minimum Measurement Range: 100 °C
|
Thermocouple N | - Maximum Measurement Range: -270 to 1300 °C
- Minimum Measurement Range: 100 °C
|
Thermocouple E | - Maximum Measurement Range: -90 to 720 °C
- Minimum Measurement Range: 100 °C
|
Thermocouple B | - Maximum Measurement Range: 500 to 1820 °C
- Minimum Measurement Range: 400 °C
|
Pt100 | - Maximum Measurement Range: -200 to 650 °C
- Minimum Measurement Range: 40 °C
|